Transfer function-based partial discharge localization in power transformers

A feasibility study

authored by
Asghar Akbari, Peter Werle, H. Borsi, Ernst Gockenbach
Abstract

A study of transfer function-based partial discharge (PD) localization in power transformers was presented. Two techniques for electric PD measurements namely, narrow band and wide band were discussed. The use of sectional winding transfer functions (SWTF) for online PD evaluation in power transformers which has several advantages was also discussed. The advantages are: localization of PD sources, discrimination between PDs inside or outside of the transformer, and evaluation of actual PD amplitudes along the winding.

Organisation(s)
High Voltage Engineering and Asset Management Section (Schering Institute)
External Organisation(s)
K.N. Toosi University of Technology (KNTU)
Type
Article
Journal
IEEE Electrical Insulation Magazine
Volume
18
Pages
22-32
No. of pages
11
ISSN
0883-7554
Publication date
09.2002
Publication status
Published
Peer reviewed
Yes
ASJC Scopus subject areas
Electronic, Optical and Magnetic Materials, Electrical and Electronic Engineering
Electronic version(s)
https://doi.org/10.1109/MEI.2002.1044318 (Access: Unknown)