Drying of Transformer Insulation using Zeolite

authored by
Issouf Fofana, V. Wasserberg, H. Borsi, Ernst Gockenbach, Masoud Farzaneh
Abstract

The drying process for upgrading transformer insulating liquids using zeolite was described. The drying efficiency of high-voltage transformers depended on process duration, environmental impact, connections between the transformer and the drying units, voltage rating and the capacity of the drying unit. The process involved the use of filter to purify the liquid which reduced source for partial discharges (PD) or breakdowns. The zeolite sensor determined the actual status of the zeolite filter by measuring the variation in conductivity or permittivity of a sensor filled with the same material.

Organisation(s)
High Voltage Engineering and Asset Management Section (Schering Institute)
External Organisation(s)
Universite du Quebec a Chicoutimi (UQAC)
Type
Article
Journal
IEEE Electrical Insulation Magazine
Volume
20
Pages
20-30
No. of pages
11
ISSN
0883-7554
Publication date
01.2004
Publication status
Published
Peer reviewed
Yes
ASJC Scopus subject areas
Electronic, Optical and Magnetic Materials, Electrical and Electronic Engineering
Electronic version(s)
https://doi.org/10.1109/MEI.2004.1266362 (Access: Closed)