Moisture uptake of mineral oil at different air relative humidities and temperatures
- authored by
- Issouf Fofana, H. Borsi, Ernst Gockenbach
- Abstract
We report here the results of the simulation of a defect in the breathing system of a high voltage transformer. These investigations serve also as fundamental ones concerning the moisture uptake velocity of mineral oil under selective conditions. The investigations were performed at a temperature of 23 and 60 °C while the surrounding air relative humidity was varied between 20 and 90% to simulate climatic variations. The results were discussed regarding the AC electric strength standard according to VDE or IEC. Finally a correlation between the surrounding air relative humidity, temperature and oil moisture uptake rate is proposed.
- Organisation(s)
-
High Voltage Engineering and Asset Management Section (Schering Institute)
- External Organisation(s)
-
Universite du Quebec a Chicoutimi (UQAC)
Hydro-Quebec
- Type
- Article
- Journal
- Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
- Volume
- 1
- Pages
- 276-279
- No. of pages
- 4
- ISSN
- 0084-9162
- Publication date
- 2000
- Publication status
- Published
- Peer reviewed
- Yes
- ASJC Scopus subject areas
- Building and Construction, Industrial and Manufacturing Engineering, Electrical and Electronic Engineering
- Electronic version(s)
-
https://doi.org/10.1109/CEIDP.2000.885280 (Access: