Moisture uptake of mineral oil at different air relative humidities and temperatures
- verfasst von
- Issouf Fofana, H. Borsi, Ernst Gockenbach
- Abstract
We report here the results of the simulation of a defect in the breathing system of a high voltage transformer. These investigations serve also as fundamental ones concerning the moisture uptake velocity of mineral oil under selective conditions. The investigations were performed at a temperature of 23 and 60 °C while the surrounding air relative humidity was varied between 20 and 90% to simulate climatic variations. The results were discussed regarding the AC electric strength standard according to VDE or IEC. Finally a correlation between the surrounding air relative humidity, temperature and oil moisture uptake rate is proposed.
- Organisationseinheit(en)
-
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
- Externe Organisation(en)
-
Université du Québec à Chicoutimi (UQAC)
Hydro-Quebec
- Typ
- Artikel
- Journal
- Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
- Band
- 1
- Seiten
- 276-279
- Anzahl der Seiten
- 4
- ISSN
- 0084-9162
- Publikationsdatum
- 2000
- Publikationsstatus
- Veröffentlicht
- Peer-reviewed
- Ja
- ASJC Scopus Sachgebiete
- Bauwesen, Wirtschaftsingenieurwesen und Fertigungstechnik, Elektrotechnik und Elektronik
- Elektronische Version(en)
-
https://doi.org/10.1109/CEIDP.2000.885280 (Zugang:
Unbekannt)