An investigation on PRPD patterns generated by the UHF measurement technique for power transformers
- verfasst von
- Mohammad Akbari Azirani, Peter Werle, Asghar Akbari Azirani, Hamid Jahangir, Janusz Marian Szczechowski
- Abstract
In this contribution, the alternative approach of applying the PRPD technique to the captured UHF signals in order to obtain an UHF PRPD pattern as a complementary tool for PD root cause analysis is investigated. For this purpose, different fault scenarios were created inside a specially designed transformer tank. The UHF signals were captured via different antennas using several measurement setups to determine how parameters such as frequency, bandwidth, PD location, etc. affect the sensitivity of the UHF measurement technique for different types of PD. Furthermore, the correlation between the captured PRPD patterns using the electrical measurement according to IEC 60270 and the UHF measurement technique were analyzed and compared. Finally, the results are presented and the advantages and flaws of the PD cause identification via the UHF PRPD technique are discussed.
- Organisationseinheit(en)
-
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
- Externe Organisation(en)
-
K.N. Toosi University of Technology (KNTU)
ABB Group
- Typ
- Aufsatz in Konferenzband
- Seiten
- 1144-1147
- Anzahl der Seiten
- 4
- Publikationsdatum
- 19.07.2017
- Publikationsstatus
- Veröffentlicht
- Peer-reviewed
- Ja
- ASJC Scopus Sachgebiete
- Elektrotechnik und Elektronik, Steuerung und Optimierung, Energieanlagenbau und Kraftwerkstechnik
- Elektronische Version(en)
-
https://doi.org/10.1109/IranianCEE.2017.7985213 (Zugang:
Geschlossen)