Investigation of the thermal transfer coefficient by the energy balance of fault arcs in electrical installations
- verfasst von
- X. Zhang, Gerhard Pietsch, Ernst Gockenbach
- Abstract
In order to determine the pressure rise due to fault arcs in electrical installations, the portion of energy heating the surrounding gas of the fault arc has to be known. The ratio of the portion of energy to the electrical energy, the thermal transfer coefficient, well known in literature as κp-factor, is adopted here. This paper presents a theoretical approach to calculate the thermal transfer coefficient κp and to determine the pressure rise in an electrical installation. It is based on the solution of the fundamental hydro- and thermodynamic conservation equations taking into account melting and evaporation of metals as well as chemical reactions with the surrounding gas of the fault arc. The results for closed arc chambers show that factors such as the kinds of insulating gas and of electrode material, the size of the test vessel, and the gas density considerably influence the thermal transfer coefficient and thus the pressure rise. Furthermore it is demonstrated, with an example of a short-circuit in a compact medium-voltage station with heavy metal evaporation, that the mathematical approach is a reliable tool to assess the development of pressure.
- Organisationseinheit(en)
-
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
- Externe Organisation(en)
-
Rheinisch-Westfälische Technische Hochschule Aachen (RWTH)
- Typ
- Artikel
- Journal
- IEEE Transactions on Power Delivery
- Band
- 21
- Seiten
- 425-431
- Anzahl der Seiten
- 7
- ISSN
- 0885-8977
- Publikationsdatum
- 01.2006
- Publikationsstatus
- Veröffentlicht
- Peer-reviewed
- Ja
- ASJC Scopus Sachgebiete
- Energieanlagenbau und Kraftwerkstechnik, Elektrotechnik und Elektronik
- Elektronische Version(en)
-
https://doi.org/10.1109/TPWRD.2005.852274 (Zugang:
Geschlossen)