Determining the test voltage factor function for the evaluation of lightning impulses with oscillations and/or an overshoot

verfasst von
Pascual Simon, Fernando Garnacho, Sonja Monica Berlijn, Ernst Gockenbach
Abstract

In order to remove the present IEC 60060-1 and IEEE Standard 4 ambiguities in the evaluation of the test voltage when oscillations and/or an overshoot appear superimposed in a lightning impulse, at the end of the 1990s, a European Project within the Standard, Measurement and Testing (SMT) program was developed by KEMA (Netherlands), Schering Institute (Germany), LCOE (Spain), and NGC (United Kingdom) in coordination with the CIGRE Working Group 33.03. The conclusion of this European Project is a new evaluation method called test voltage function K(f) derived on the breakdown behavior of different dielectric media, that removes the standard ambiguity to determine the test voltage of an impulse with oscillations and/or an overshoot. This paper presents the experimental results of the project and deals in depth with the definition of K(f).

Organisationseinheit(en)
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
Externe Organisation(en)
KEMA Nederland B.V.
Typ
Artikel
Journal
IEEE Transactions on Power Delivery
Band
21
Seiten
560-566
Anzahl der Seiten
7
ISSN
0885-8977
Publikationsdatum
04.2006
Publikationsstatus
Veröffentlicht
Peer-reviewed
Ja
ASJC Scopus Sachgebiete
Energieanlagenbau und Kraftwerkstechnik, Elektrotechnik und Elektronik
Elektronische Version(en)
https://doi.org/10.1109/TPWRD.2005.858807 (Zugang: Unbekannt)