Experience with partial discharge, dissipation factor and recovery voltage measurements for the evaluation of insulation systems of high voltage rotating machines

verfasst von
Mohsen Farahani, H. Borsi, E. Gockenbach
Abstract

The possibilities and limitations of partial discharge (PD), recovery voltage (RV) and dissipation factor measurement for evaluation of the actual status of insulation system of high voltage rotation machines were presented. The dielectric dissipation of insulation was found to cause by insulation resistance and relaxation polarization alongwith the interface polarization and partial discharges. The results confirmed the sensitivity of partial discharge measurement on the thermal ageing.

Organisationseinheit(en)
Fachgebiet Hochspannungstechnik und Asset Management (Schering-Institut)
Typ
Konferenzaufsatz in Fachzeitschrift
Journal
Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Annual Report
Seiten
454-457
Anzahl der Seiten
4
ISSN
0084-9162
Publikationsdatum
2002
Publikationsstatus
Veröffentlicht
Peer-reviewed
Ja
ASJC Scopus Sachgebiete
Elektrotechnik und Elektronik, Wirtschaftsingenieurwesen und Fertigungstechnik, Bauwesen